IDAX300 and IDAX350 Insulation Diagnostic Analysers
The IDAX300 and IDAX350 insulation diagnostic analysers are insulation diagnostic instruments based on DFR (Dielectric Frequency Response), also known as FDS (Frequency Domain Spectroscopy). DFR is a measurement technique in which capacitance and losses (dissipation factor/tan delta or power factor) is measured over multiple frequencies to assess insulation condition in test objects such as power transformers, bushings, and instrument transformers. DFR technology is an established test procedure in laboratories that Megger has adapted for field use in the IDAX range of instruments.
This IDAX series consists of:
For extended applications, the IDAX interfaces seamlessly with the VAX020 high voltage amplifier for 2 kV.
In these instruments, the IDAX software incorporates a new ITC corrected frequency sweep specifically designed for assessment of instrument transformers and bushings. Thanks to a novel approach to the combination of time and frequency domain data, the IDAX provides the shortest measurement time in the marketplace for a full DFR measurement from 1 kHz to 10 μHz. Separate reference models are fitted to each data set (time or frequency) prior to transformation and combination, which eliminates the risk of artifacts introduced by approximations or transformation of incomplete data sets.
General
Mains voltage: 100 – 240 V ±10 %, 50 / 60 Hz
Power consumption: 250 VA (max)
Measurement section
Inputs: Red, blue, ground
Capacitance range: 10 pF – 100 μF
Inaccuracy: 0.5 % + 1 pF
Tan delta range: 0 - 100 (with retained accuracy of capacitance; otherwise higher)
Power factor range: 0 - 1 (with retained accuracy of capacitance; otherwise higher)
Inaccuracy:
IDAX300 (at 200 Vpeak):
>1000 pF: 0.5 % of rd + 0.01 % absolute
>300 pF: 0.5 % of rd + 0.02 % absolute
>10 pF: 0.5 % of rd + 0.10 % absolute
With VAX020 amplifier (at 2 kVpeak):
>100 pF: 0.5 % of rd + 0.01 % absolute
>30 pF: 0.5 % of rd + 0.02 % absolute
>10 pF: 0.5 % of rd + 0.03 % absolute
Max AC interference:
1 mA, 1:10 SNR (IDAX)
10 mA, 1:10 SNR (VAX020)
Max DC interference:
2 μA (IDAX) 20 μA (VAX020)
Typical measurement durations
DFR | PDC | Equiv. freq. range | Time
1 kHz-10 mHz | — | 1 kHz - 10 mHz | 5 min
1 kHz- 1 mHz | — | 1 kHz - 1 mHz | 36 min
1 kHz- 1 mHz | — | 1 kHz - 1 mHz | 23 min
1 kHz - 0.1 Hz | 1000 s | 1 kHz - 1/0.1 mHz | 18 min
1 kHz - 0.1 Hz | 10000 s | 1 kHz - 100/10 μHz | 2 h 55 min
Time domain current measurement (PDC)
Range: ±50 mA
Resolution: 0.1 pA
Inaccuracy: 0.5% ±1 pA
Input resistance (DC mode): ≤10 kΩ
Outputs
Generator:
Voltage/current ranges, 10 V: 0 – 10 Vpeak, 0 – 50 mA peak
Voltage/current ranges, 200 V: 0 – 200 Vpeak, 0 – 50 mA peak
Frequency range: DC, 0.1 mHz - 10 kHz
External:
For external amplifier: E.g,. VAX020